The applications can generate requirements and errors in the Open BIM workflow:
These messages appear in several places:
The following table shows the implemented requirements and errors, and the version as of which they have been included in the corresponding BIM programs:
Type | Origin application | Reception application | Title | Description | Version |
---|---|---|---|---|---|
Requirement | CYPEDOC CTE HS2 | CYPELEC REBT | CTE DB HS 2 (apartado 2.1.3.d) |
Container warehouses must have a fixed plug base of 16A 2p + T according to UNE 20.315: 1994. | 2019.f |
Requirement | CYPEDOC CTE HS2 | CYPEFIRE CTE | CTE DB HS 2 (apartado 2.1.3.e) |
The container storage areas must meet the fire protection conditions established for the waste storage areas in section 2 of Section SI-1 of DB-SI Safety in case of fire. | 2019.f |
Requirement | CYPEDOC CTE HS2 | CYPELUX CYPELUX CTE CYPELUX RECS |
CTE DB HS 2 (apartado 2.1.3.d) |
Container storage areas must have artificial lighting that provides at least 100 lux at 1 m above ground level. | 2019.d |
Requirement | CYPEDOC CTE HS2 | CYPEPLUMBING Sanitary Systems | CTE DB HS 2 (apartado 2.1.3.c) |
Container storage areas must have at least one antifouling siphon sink in the ground. | 2019.e |
Requirement | CYPEDOC CTE HS2 | CYPEPLUMBING Water Systems | CTE DB HS 2 (apartado 2.1.3.c) |
Container storage areas must have at least one water inlet equipped with a shut-off valve. | 2019.e |
Requirement | CYPEDOC CTE HS2 | CYPETHERM HE Plus | CTE DB HS 2 (apartado 2.1.3.a) |
The location and design of the container warehouses must be such that the interior temperature does not exceed 30°C. | 2019.e |
Requirement | CYPEFIRE CTE | Open BIM CTE HS 3 | CTE DB SI 3 (apartado 8.2.a) |
The fire smoke control system in the parking area must be designed in accordance with UNE 23 585: 2017 or, when the ventilation system is mechanical and in accordance with DB HS 3, it must be capable of extracting an air flow of 150 l/parking space ·s with a maximum contribution of 120 l /parking space square·s. | 2019.f |
Requirement | CYPEFIRE CTE CYPEFIRE Design |
CYPEFIRE Sprinklers | Instalación automática de extinción | CYPEFIRE CTE or CYPEFIRE Design users have foreseen an automatic fire extinguishing installation in the space. | 2019.d |
Requirement | CYPELEC CT | CYPEFIRE CTE | CTE DB SI 1 (apartado 2) |
Users must meet the fire protection conditions established for transformer centers in section 2 of Section SI-1 of DB-SI Safety in case of fire. | 2019.f |
Requirement | Open BIM CTE SUA 8 | Open BIM Lightning | CTE DB SUA 8 | According to the verification procedure described in CTE DB SUA 8, a lighting protection system must be installed in the building. | 2019.d |
Error | Open BIM Accessibility | IFC Builder CYPECAD MEP |
The clear width of the door is less than that stated by the design code. | 2019.f |